Permit: T07EL00242

Parcel: 116210250


Addresses:

1024 W CONGRESS ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/09/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/06/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/16/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT INSTALL A PANEL IN A CLOSET
2. USE ALL GE BREAKERS IN PANEL
3. ISOLATE NEUTRAL AND GROUNDS IN SUB-PANEL
4. THERE IS NO NEUTRAL IN SUB-PANEL
5. OUTSIDE SERVICE IS ONLY 100 AMP

SCHEDULE KILL WITH TEP
CALL INSPECTOR ON SAME DAY TO INSPECT NEW SERVICE
ONCE INSPECTION OK'S HE CALL TEP