Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/29/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BUILDING INSPECTOR TO CONTACT OWNER ABOUT INTERIOR WORK. CONTRACTORS SCOPE OF WORK IS COMPLETE OWNER TO ADDRESS OTHER CONCERNS. |
|
| 03/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. AN APPROVED & LISTED BRACE KIT IS NEEDED FOR RISER 2. VERIFY CONDUCTOR DERATING PER 310.15 3. SPLIT BOLT ONLY LISTED FOR 2 CONDUCTORS A RUN & A TAP 4. CONDUCTORS #8 & LARGER IN A RACEWAY TO BE STRANDED 5. PLEASE VERIFY PERMITS FOR NEW WIRING TO INTERIOR 6. MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 110.26 7. RISER HARDWARE TO BE 1/4" MINIMUM |