Permit: T07EL00239

Parcel: 126040650


Addresses:

814 N CATALINA AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/29/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BUILDING INSPECTOR TO CONTACT OWNER ABOUT INTERIOR WORK.

CONTRACTORS SCOPE OF WORK IS COMPLETE OWNER TO ADDRESS OTHER CONCERNS.
03/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. AN APPROVED & LISTED BRACE KIT IS NEEDED FOR RISER
2. VERIFY CONDUCTOR DERATING PER 310.15
3. SPLIT BOLT ONLY LISTED FOR 2 CONDUCTORS
A RUN & A TAP
4. CONDUCTORS #8 & LARGER IN A RACEWAY TO BE STRANDED
5. PLEASE VERIFY PERMITS FOR NEW WIRING TO INTERIOR
6. MAINTAIN WORKING CLEARANCE IN FRONT OF
SERVICE 110.26
7. RISER HARDWARE TO BE 1/4" MINIMUM