Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1. OK TO CLEAR INCREASE & RELOCATE -- CALL FOR FINAL ONCE SERVICE SWITCHED 2. AT FINAL STRAP GROUND WIRE BELOW SERVICE 3. SWITCH GAS & WATER BONDS AT TIME OF SERVICE SWITCH |
|
| 06/29/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE A LISTED MAST BRACE -- NOT EMT 2. STAND OFF PIECE BROKEN IN METER SECTION 3. BOND WATER & GAS PIPES TO SERVICE 4. INSTALL ADDRESS ON SERVICE 5. OK UFER TO ADDITION FOOTING |
|
| 03/08/2007 | ELECTRIC - SERVICE UPGRADE | Cancelled | IVRS - RI canceled |