Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07EL00230

Parcel: 113100610


Addresses:

2625 N MARTIN AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/19/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
1. OK TO CLEAR INCREASE & RELOCATE -- CALL FOR FINAL ONCE SERVICE SWITCHED
2. AT FINAL STRAP GROUND WIRE BELOW SERVICE
3. SWITCH GAS & WATER BONDS AT TIME OF SERVICE SWITCH
06/29/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE A LISTED MAST BRACE -- NOT EMT
2. STAND OFF PIECE BROKEN IN METER SECTION
3. BOND WATER & GAS PIPES TO SERVICE
4. INSTALL ADDRESS ON SERVICE
5. OK UFER TO ADDITION FOOTING
03/08/2007 ELECTRIC - SERVICE UPGRADE Cancelled IVRS - RI canceled