Permit: T07EL00228

Parcel: 104060520


Addresses:

1870 W PRICE ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/08/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/07/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BONDING CONDUCTOR FOR CT CAN, SERVICE NIPPLE UNDERSIZED -- NEC 250.102D
2. IDENTIFY SERVICE DISCONNECT AS A
"SERVICE DISCONNECT" - NEC 230.70B
3. INSTALL ADDRESS ON SERVICE
4. GROUND RODS TO BE MINIMUM 6' APART AND PROVIDE PHYSICAL PROTECTION FOR GROUNDING ELECTRODE CONDUCTOR - NEC 250.56
5. BOND WATER, GAS (IF ANY) AND BUILDING STEEL -
NEC 250.104
6. TIGHTEN CONNECTIONS
7. NO SPLICE ALLOWED UNDER BUSHING LUG IN PANEL -
NEC 110.3
8. MINIMUM #4 CU EQUIPMENT GROUND TO PANEL -
NEC 250.122