Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/08/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/07/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BONDING CONDUCTOR FOR CT CAN, SERVICE NIPPLE UNDERSIZED -- NEC 250.102D 2. IDENTIFY SERVICE DISCONNECT AS A "SERVICE DISCONNECT" - NEC 230.70B 3. INSTALL ADDRESS ON SERVICE 4. GROUND RODS TO BE MINIMUM 6' APART AND PROVIDE PHYSICAL PROTECTION FOR GROUNDING ELECTRODE CONDUCTOR - NEC 250.56 5. BOND WATER, GAS (IF ANY) AND BUILDING STEEL - NEC 250.104 6. TIGHTEN CONNECTIONS 7. NO SPLICE ALLOWED UNDER BUSHING LUG IN PANEL - NEC 110.3 8. MINIMUM #4 CU EQUIPMENT GROUND TO PANEL - NEC 250.122 |