Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SPLIT BREAKER INSTALLED IS NON CTL AND IS FOR REPLACEMENT USE ONLY. INSTALL SPLIT BREAKER WITH REJECTION TAB NEC 110.3
2) NEUTRAL CONDUCTORS #6 AND SMALLER TO BE MARKED CONTINOUSLY NEC 200.6
3) GROUNDING CONDUCTORS #6 AND SMALLER TO BE MARKED CONTINOUSLY NEC 250.119
4) SEAL OPENING IN BACK OF PANEL WITH NON COMBUSTIBEL MATERIAL
05/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
1. INSTALL BUSHING TO PROTECT WIRES THROUGH BACK OF OLD FPE PANEL
2. CANNOT USE GREEN WIRE FOR PHASE CONDUCTORS
NEC 310.12
3. 14 CURRENT CARRYING CONDUCTORS IN 1" EMT NEED TO DERATE PER NEC 310.15
4. INSTALL PANEL DIRECTORY PER NEC 408.4
5. LABEL OLD FPE PANEL JUNCTION BOX ONLY
6. REMOVE PAINT AT GROUND CLAMP CONNECTION ON GAS PIPE PER NEC 250.12