Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. SCHEDULE SEAL HOLE GRID J-BOX W/#10 |
|
| 02/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE OLD 60 AMP SWITCH BOX AND INSTALL A WEATHERPROOF JUNCTION BOX & SPLICE WIRING WITH APPROVED METHODS, OLD BOX HAS A LARGE HOLE ON TOP SEAL UNTIL CORRECTIONS MADE 2. REMOVE OLD GROUND ONCE OLD DISCONNECT REMOVED 3. STRAP BOTH 3/4" CONDUITS GOING UP ROOF WITHIN 3" OF ENCLOSURES. |