Permit: T07EL00212

Parcel: 125112410


Addresses:

3805 E 5TH ST #13

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/29/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. CONTRACTOR STATES NO NEW WORK WAS DONE
ONLY REPLACED DEVICES.
06/27/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT CONNECT GROUNDING CONDUCTOR TO PANEL ENCLOSURE USING SHEETMETAL SCREWS - NEC 250.8
2. GROUNDING CONDUCTORS & NEUTRALS TO BE SEPARATED AT PANEL. NEC 250.24, 250.142
3. APPEARS THAT ENTIRE UNIT HAS BEEN REWIRED
PLEASE VERIFY PERMIT FOR ALL WORK THAT WAS DONE TO UNIT.