Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/30/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED A PERMIT FOR SERVICE UPGRADE ALSO,
2. MAST ABOVE ROOM WILL REQUIRE 2 LISTED & APPROVED GUY BACK BRACES & LEVEL RISER.
3. GROUNDING SYSTEM FOR SERVICE REQUIRES 2 RODS 6' APART PLUS WATER & GAS BOND
GROUND WIRE TO BE BURNED AT LEAST 2"
4. RISER TO BE SUPPORTED BELOW SERVICE ALSO,
5. SMOKE DETECTORS REQUIRED IN BEDROOMS
6. INSTALL ALL MISSING FIXTURES
7. KITCHEN COUNTER RECEPTACLES BY SINK TO BE GFI
8. HOUSE NOT OWNER OCCUPIED
NEED AN ELECTRICAL CONTRACTOR TO REDO SERVICE.