Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) GFI BELOW SERVICE CANNOT BE SUPPORTED BY FITTING ONLY-OFF SET NIPPLE TO WOOD AND ANCHOR GFI 2) CALL FOR FINAL ONCE ENERGIZED AND COMPLETE |
|
| 02/27/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SCH 80 ONLY TO BE USED OUTSIDE EXPOSED 2. 1/2" PVC OUT OF SERVICE TO TRAILER TO BE SCH80 ABOVE GROUND AND SUPPORTED, ALSO, PHYSICALLY PROTECTED TO TRAILER NOT HOSE OVER IT. 3. WHITE WIRE USED AS AC HOT LEG TO BE TAPED BLK, INSTALL ALL STRANDS OF BLK INTO BREAKER SERVICE LOOKS OK -- CORRECT ABOVE & RECALL |
|
| 02/23/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* WILL RESCHEDULE |