Permit: T07EL00193

Parcel: 122150310


Addresses:

3301 E LINDEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/31/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
11/27/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TWO POLE BREAKER TO FEED SUB PANEL
2) IDENTIFY WHAT BREAKERS ARE FOR
3) OPEN WIRING NOT ALLOWED INTO SUB-PANEL USE RACEWAY OR ROMEX
4) SEPERATE NEUTRALS AND GROUNDS IN SUB PANEL AND INSTALL COVER SCREWS
03/19/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) INSTALL LINE SIDE AS PER MANUFACTURER
2) MOVE NEUTRAL MARKINGS CLOSER TO WEATHER HEAD