Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND RODS TO BE MINIMUM 6' APART NEC 250.56 2) GROUNDING ELECTRODE CONDUCTOR TO SERVICE NOT INSPECTED BEFORE COVERED IN WALL 3) CANNOT LOCATE WATER AND GAS BOND 4) PROVIDE PERMIT FOR NEW INTERIOR WIRING |