Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) YOU NEED 36" IN FRONT OF SERVICE 2) TEP TO MOVE OH TAP OK 3) MOVING OF MID TAP FROM TEP MAY CLEAR ISSUE #3 |
|
| 02/01/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED/CORRECTIONS NOT COMPLETE |
|
| 01/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SERVICE DOES NOT HAVE PROPER WORKING CLEARANCE - NEC 110.26 2. SERVICE DROP DOES NOT HAVE PROPER CLEARANCE OVER ROOF - NEC 230.24 3. SERVICE DROP DOES NOT HAVE PROPER CLEARANCE TO POOL - NEC 680.8 4. NEED PROPER CONNECTOR FOR SUB-PANEL FEEDER AND DON'T PINCH CONDUCTORS - NEC 300, 314 5. SECURE TO WALL AND BURY GROUNDING ELECTRODE CONDUCTOR - NEC 250.64 6. CORRECLTY IDENTIFY CKT'S ON PROVIDED PANEL DIRECTORY - NOT SHARPIE - NEC 408.4 7. PROVIDE COMPLETE RAEWAY FOR CONDUCTORS IN L.B AND INSTALL L.B COVER SCREW NEC 300.16, 300.18 8. PROVIDE A LISTED GUY KIT FOR MAST (NOT EMT) AND SECURE INTO STRUCTURE, NOT ROOF SHEATHING - NEC 230.28 9. TIGHTEN BOND CLAMP SET SCREWS |