Permit: T07EL00178

Parcel: 122150830


Addresses:

3120 E LINDEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) YOU NEED 36" IN FRONT OF SERVICE
2) TEP TO MOVE OH TAP OK
3) MOVING OF MID TAP FROM TEP MAY CLEAR ISSUE #3
02/01/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED/CORRECTIONS NOT COMPLETE
01/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. SERVICE DOES NOT HAVE PROPER WORKING CLEARANCE - NEC 110.26
2. SERVICE DROP DOES NOT HAVE PROPER CLEARANCE OVER ROOF - NEC 230.24
3. SERVICE DROP DOES NOT HAVE PROPER CLEARANCE TO POOL - NEC 680.8
4. NEED PROPER CONNECTOR FOR SUB-PANEL FEEDER AND DON'T PINCH CONDUCTORS - NEC 300, 314
5. SECURE TO WALL AND BURY GROUNDING ELECTRODE CONDUCTOR - NEC 250.64
6. CORRECLTY IDENTIFY CKT'S ON PROVIDED PANEL DIRECTORY - NOT SHARPIE - NEC 408.4
7. PROVIDE COMPLETE RAEWAY FOR CONDUCTORS IN L.B AND INSTALL L.B COVER SCREW NEC 300.16, 300.18
8. PROVIDE A LISTED GUY KIT FOR MAST (NOT EMT) AND SECURE INTO STRUCTURE, NOT ROOF SHEATHING -
NEC 230.28
9. TIGHTEN BOND CLAMP SET SCREWS