Permit: T07EL00167

Parcel: 10602212A


Addresses:

131 W PASTIME RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROPERLY TAP SCREWS FOR GROUND BAR - SCREWS DO NOT TIGHTEN DOWN
2. STILL NEED PROPER CONNECTOR OR BUSHING WHERE CONDUCTORS ENTER BACK OF SUB-PANEL
3. TAP GROUND BAR SCREWS IN J-BOX (SAME AS #1)
09/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IN SUB-PANEL PROVIDE PROPER GROUND BAR TO TERMINATE ALL EQUIPMENT GROUNDS
2. #6 NEUTRAL TO BE WHITE ENTIRE LENGTH
3. MULTI-WIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES
4. PROVIDE PROPER CONNECTORS FOR ROMEX ENTERING ENCLOSURE TO J-BOX

1. STRAP EMT
2. GROUND J-BOX
3. NEED SEALING TYPE LOCKNUT INTO SERVICE ENCLOSURE

AT SERVICE
1. PANEL DIRECTORY TO BE CORRECT
2. OVERCURRENT PROTECTION TO HIGH FOR #6 FEEDER TO SUB-PANEL (HAVE 90 AMP BREAKER ON #6?)
3. RECONNECT GROUNDS FOR PHONE & CATV