Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROPERLY TAP SCREWS FOR GROUND BAR - SCREWS DO NOT TIGHTEN DOWN 2. STILL NEED PROPER CONNECTOR OR BUSHING WHERE CONDUCTORS ENTER BACK OF SUB-PANEL 3. TAP GROUND BAR SCREWS IN J-BOX (SAME AS #1) |
|
| 09/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IN SUB-PANEL PROVIDE PROPER GROUND BAR TO TERMINATE ALL EQUIPMENT GROUNDS 2. #6 NEUTRAL TO BE WHITE ENTIRE LENGTH 3. MULTI-WIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES 4. PROVIDE PROPER CONNECTORS FOR ROMEX ENTERING ENCLOSURE TO J-BOX 1. STRAP EMT 2. GROUND J-BOX 3. NEED SEALING TYPE LOCKNUT INTO SERVICE ENCLOSURE AT SERVICE 1. PANEL DIRECTORY TO BE CORRECT 2. OVERCURRENT PROTECTION TO HIGH FOR #6 FEEDER TO SUB-PANEL (HAVE 90 AMP BREAKER ON #6?) 3. RECONNECT GROUNDS FOR PHONE & CATV |