Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE TO BE MADE RAIN TITE ON AREAS ABOVE LIVE PARTS ( 1/2" KO ON TOP AND GROUND ON SIDE ) 2) STILL NO MAST BRACE ?, STRUT NOT PROPERLY SECURED TO STRUCTURE |
|
| 01/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. TOP OF SERVICE TO BE RAINTIGHT - SINGLE GROUND NOT ALLOWED, USE MYERS TYPE HUB OR SEALING LOCKNUTS FOR RACEWAYS. 2. 3/4 EMT OVERFILLED GOING TO J-BOX 3. GROUND J-BOX 4. NEED BUSHING #4 AND LARGER WIRE 5. TIGHTEN ALL FITTINGS & LOCKNUTS 6. PROVIDE LISTED GUY KIT FOR MAST |
|
| 01/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ACCESS -- NO ONE HOME PLEASE RECALL AND LEAVE MESSAGE FOR INSPECTION. |