Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/02/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR INSPECTION AFTER TEP TIE IN |
|
| 02/28/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. WATER & GAS BONDING TO TERMINATE AT NEW SERVICE GROUNDING ELECTRODE SYSTEM PER 250 NEC 2. BRACE FOR RISER CONDUIT MUST BE A LISTED ASSEMBLY SMASHED ENDS ON EMT CONDUIT NOT APPROVED |