Permit: T07EL00130

Parcel: 121101500

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/31/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
NO ACCESS -- FINISH #1 & 2 PREVIOUS INSPECTION
07/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20
2. SECURE CABLE TO ENCLOSURE A/C DISCONNECT - 312.5
3. CORRECTLY IDENTIFY UNGROUNDED AND GROUNDED OR GROUNDING CONDUCTORS - AC
4. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8
5. FINISH #1 OF PREVIOUS INSPECTION
06/19/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK GARAGE
1. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL
WITH A NON-COMBUSTIBLE PRODUCT
02/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) A PERMIT FOR REWIRING OF INTERIOR IS NEEDED. PLEASE ADD 02062 TEMP SERVICE TO PERMIT TO CLEAR
2) PLEASE VERIFY GAS BONDING
3) LABEL BREAKER
4) CHASE NIPPLE NOT AN APPROVED FITTING