Permit: T07EL00125

Parcel: 136252860


Addresses:

6760 E FAYETTE ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/07/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/22/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. #4 GROUND TO TERMINATE IN LOAD SIZE OF SERVICE
2. BRACE FOR RISER CONDUIT MUST BE LISTED
HOMEMADE NOT APPROVED
02/15/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO INSTALL A LISTED AND APPROVED GUY BACK SUPPORT -- RIGID CONDUIT TYPE.
2. NEED TO INSTALL SERVICE ENTRANCE CONDUCTORS IN RISER TO SERVICE.
3. CANNOT HAVE 3 GROUND WIRES UNDER ONE LUG.
4. GROUND SYSTEM NOT INSPECTED - CANNOT USE PICTURE
5. GROUND WIRES BELOW SERVICE NEED TO BE SUPPORTED
6. NEED TO INSPECT DRYER OUTLET AND DRYER CONDUIT TO BE SUPPORTED WITHIN 3' OF PANEL.
7. WHERE IS PERMIT FOR ADDITION? PLEASE POST
8. WATER BOND AND GAS BOND TO BE #4 CU