Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 02/26/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 2 #4 GROUND WIRE IN PNL LUG - ONLY ONE PER TERMINAL 2. STRAP GROUND TO WALL - NEED 2 RODS 6' APART 3. ACORN LUG ON GROUND ROD - ONLY 1 WIRE AND INSTALL ON POINT SIDE NOT BOLT SIDE. |