Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/27/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 02/23/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/01/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NOT A COMPLETE UPGRADE AS REQUIRED, SERVICE ENTRANCE CONDUCTORS ARE #1 AC = 130 amps, WIRES IN METER & RISER NEED TO BE 200 A 2. GROUND RODS TO BE TIED TOGETHER WITH UNSPLICED #4 CU 3. USE ROMEX CONNECTOR WHERE BONDS ENTER BOTT 4. #4 COPPER AT GROUND ROD CLAMPS TO BE ON CURVED SIDE & RETIGHTEN 5. IMPROPER FITTINGS USED TO CONNECT LB'S 6. NEED TO SUPPORT RECEPTACLE BELOW SERVICE 7. CANNOT BLOCK LB COVER ON WEST SIDE OF PNL 8. ADDRESS PNL 9. FIX ENTRY OF 3/4" CONDUIT ON EAST SIDE 10. ONLY ONE WIRE PER LUG 11. ENTRY INTO BREAKER CLEANLY |