Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RISER BRACE ON ROOF MUST BE A LISTED ASSEMBLY HOMEMADE OUT OF SMASHED EMT NOT APPROVED. 2. CHASE NIPPLES NOT ALLOWED UNLESS LOCKNUT ON BOTH SIDES. 3. GROUNDS IN J-BOX NOT TERMINATED PER CODE, ALSO, DO NOT USE SHEETMETAL SCREW TO TERMINATE GROUND WIRE USE THREADED BOLT OR NUT & BOLT, SCRAP OFF ENAMEL. 4. USE BUSHINGS WHEN GOING THRU J-BOXES TO PROTECT CABLE FROM ABRASION. |
|
| 06/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CALLED PH# PER REQUEST NO ANSWER DOG IN YARD - NO ANSWER AT DOOR RECALL INSP. |