Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LOOSE RECEPT & COVER ON NORTH OUTSIDE WALL 2. INSTALL BRACE FOR COOLER BOX ON ROOF 3. GARAGE LIGHT LOOSE 4. FANS IMPROPERLY WIRED IN LIVING ROOM AND LARGE BEDROOM - CANNOT HAVE ZIP CORD COMING OUT OF FAN BASE TO RECEPTACLE. 5. THERMOSTAT IN HALL TO BE RE-SUPPORTED 6. LIGHT IN NE CLOSET OF BEDROOM AT NORTHEAST SIDE REQUIRED TO HAVE AN ENCLOSURE AROUND BULB. |
|
| 01/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CALL PH. #808-5305 - LEFT MESSAGE SEE NOTES LAST INSP. NO KEY LEFT PER MESSAGE A REINSP. FEE WILL BE ASSESSED NEXT INSP. IF NO COMPLIANCE. |
|
| 01/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. LOOSE RECEPT & COVER ON NORTH OUTSIDE WALL. 2. INSTALL BRACE FOR COOLER BOX ON ROOF. 3. BLD. LOCKED - CALLED 808-5305 PER REQUEST, LEFT MESSAGE WITH ETA FOR INSPECTION. RECALL WHEN ACCESS AVAILABLE 9:35 AM |