Permit: T07EL00096

Parcel: 12002118B


Addresses:

3926 S 14TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECEPTACLE OVER SINK NEEDS TO BE GFI
02/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE IS OK, THIS PERMIT IS FOR RECONNECT, MUST BE OPEN FOR INSPECTION
01/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
CALLED PER MESSAGE AT 7;24 AM LEFT ETA FOR INSPECTOR ON MESSAGE.

1. BLD. LOCKED
2. OLD 110V 30 AMP SERVICE IS OUTDATED, HAS WATER DAMAGE DUE TO BEING RATED FOR INDOORS USE - REPLACE WITH 100 AMP UPGRADE MIN. PER CODE.
3. OUTSIDE RECEPTACLES UNDER PORCH IN BACK SHOULD BE GFI PROTECTED.
4. RECALL INSP. WHEN ACCESS AVAILABLE

8:15 AM