Permit: T07EL00095

Parcel: 11706018B


Addresses:

219 N 1ST AV

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/24/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. REMOVE BOND SCREW IN SUB-PANEL - NEC 250.24 A 5
2. INSTALL ADDRESS ON PANEL - CITY
3. PROVIDE ARC FAULT PROTECTION FOR SMOKE DETECTORS NEC 210.12 B
4. SECURE/SUPPORT ROMEX IN BASEMENT - NEC 334.30
5. EXTERIOR J-BOX IS OVERFILLED, ROMEX TO - NEC 314.16
BE CONNECTED TO METAL BOXES WITH A ROMEX CONNECTOR.
6. MAKE SURE ALL SWITCHES GROUNDED AND ALL FACEPLATE SCREWS INSTALLED, IDENTIFY WHITE USED AS HOT.

IN ATTIC
1. PROTECT ROMEX BY ACCESS - NEC 334.23
2. STAPLE ROMEX INTO BOXES - NEC 334.30