Permit: T07EL00090

Parcel: 125122150


Addresses:

3481 E EDGEMONT ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/25/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1. RISER TO BE IMC OR RIGID NOT EMT
2. GROUNDING OK -- BONDING H2O & GAS LINE OK
3. INTERIOR CONDUITS TO BE SUPPORTED - WASH ROOM
4. FINISH WASH ROOM AND COVER ALL ELECTRIC
5. COVER ALL INSIDE DEVICES J-BOXES
6. PHYSICALLY PROTECT EXPOSED ROMEX IN WASHROOM.
05/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. METAL NOT APPROVED FOR EXTENDER RING.
2. USE APPROVED HARDWARE - NOT DRYWALL OR SHEETMETAL TO HANG FAN BOX & WOOD SUPPORTS.
3. SEPARATE GROUNDS & NEUTRALS 250.24
4. BREAKER CONNECTIONS LIMITED TO SIZE OF CONDUCTOR.
05/21/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CANNOT USE SHEETMETAL SCREWS FOR GROUND CONNECTIONS.
2. INSTALL #10 GAUGE WIRE TO GROUND METAL BOX AT DRYER
3. BOXES FOR CEILING FANS TO BE LISTED & MARKED
4. DEVICE BOXES MORE THAN 1/4" BACK FROM SURFACE WILL REQUIRE EXTENSIONS.
5. OK ALL OTHER DEVICE BOXES IN HOUSE
6. OK GROUND RODS FOR SERVICE. STILL NEED FULL SERVICE INSPECTION
04/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK U.G UF OUTSIDE & STUB UP INTO HOUSE
03/02/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. VERIFY J-BOXES & LB'S LISTED FOR DIRECT BURIAL
2. TYPE NM ROMEX NOT APPROVED FOR UNDERGROUND USE
PER NEC 334
3. MIN COVER PER 300.5 NEC 18" FOR PVC CONDUIT

CHANGE TO GENERAL INSPECTORS SFR -
WORK DONE INSIDE & OUT