Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1. RISER TO BE IMC OR RIGID NOT EMT 2. GROUNDING OK -- BONDING H2O & GAS LINE OK 3. INTERIOR CONDUITS TO BE SUPPORTED - WASH ROOM 4. FINISH WASH ROOM AND COVER ALL ELECTRIC 5. COVER ALL INSIDE DEVICES J-BOXES 6. PHYSICALLY PROTECT EXPOSED ROMEX IN WASHROOM. |
|
| 05/24/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. METAL NOT APPROVED FOR EXTENDER RING. 2. USE APPROVED HARDWARE - NOT DRYWALL OR SHEETMETAL TO HANG FAN BOX & WOOD SUPPORTS. 3. SEPARATE GROUNDS & NEUTRALS 250.24 4. BREAKER CONNECTIONS LIMITED TO SIZE OF CONDUCTOR. |
|
| 05/21/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CANNOT USE SHEETMETAL SCREWS FOR GROUND CONNECTIONS. 2. INSTALL #10 GAUGE WIRE TO GROUND METAL BOX AT DRYER 3. BOXES FOR CEILING FANS TO BE LISTED & MARKED 4. DEVICE BOXES MORE THAN 1/4" BACK FROM SURFACE WILL REQUIRE EXTENSIONS. 5. OK ALL OTHER DEVICE BOXES IN HOUSE 6. OK GROUND RODS FOR SERVICE. STILL NEED FULL SERVICE INSPECTION |
|
| 04/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK U.G UF OUTSIDE & STUB UP INTO HOUSE |
|
| 03/02/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. VERIFY J-BOXES & LB'S LISTED FOR DIRECT BURIAL 2. TYPE NM ROMEX NOT APPROVED FOR UNDERGROUND USE PER NEC 334 3. MIN COVER PER 300.5 NEC 18" FOR PVC CONDUIT CHANGE TO GENERAL INSPECTORS SFR - WORK DONE INSIDE & OUT |