Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00085
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/22/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CALL IN FOR FINAL AFTER TIE-IN 2) LABEL PANELS AS TO SOURCE OR FEED 3) INSTALL SPLIT BOLT FOR GROUND TAP |