Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00075
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COVER MUST OPEN COMPLETELY & LOCK OPEN 2. CANNOT DOUBLE LUG AT SERVICE 3. CANNOT MIX COPPER & ALUM 4. CANNOT VERIFY GROUND SYSTEM - 2 GROUND RODS 6' APART 5. ADDRESS SERVICE 6. NEED AN APPROVED LOCKNUT & JUMPER FROM GROUND BUSHING TO ENCLOSURE. 7. INSTALL FUSING 8. 4/0 ALUM TO BE FUSED AT 200A 4/0 CU PRIM 4/0 ALUM SEC |