Permit: T07EL00062

Parcel: 121061400


Addresses:

5830 E CAMDEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/24/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/23/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
12/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH PREVIOUS ITEMS
2. PROTECT NM CABLE IN WALLS
12/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) GARAGE: SECURE CABLES TO BOXES
2) SECURE CABLES WITH IN 8" OF SINGLE AND 12" OF 2 ? BOXES
3) SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE
4) A MAIN DISCONNECTING MEANS IS NEEDED 2ND STRUCTURE 225.31
-----------------------------------------------------------------------------------------------
1) MAIN HOUSE: BREAKERS TO BE LISTED FOR USE BY MANUFACTURER
2) PLEASE VERIFY PERMIT FOR NEW ELECTRIC WIRE TO INTERIOR
06/04/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. A PERMANENT METAL ADDRESS LABEL
2. FINISH DRIVING GROUND RODS BELOW SURFACE
3. FILL UNUSED PORTION OF OPENINGS IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT. ALSO, FILL UNUSED OPENING IN BOTTOM OF PANEL.
4. PLEASE VERIFY PERMITS FOR NEW WIRING TO INTERIOR.