Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 01/08/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. CHASE NIPPLE NOT ALLOWED FOR USE WITH L.L 2. BOND BUSHING NEEDED AT JUNCTION BOX 3. L.L & BOX TO BE CAPABLE OF BEING LOCKED ON SERVICE FEED SIDED 4. BRACING FOR RISER TO BE A RIGID SUPPORT KIT 5. CONDUCTOR TO BE MARKED "SUNLIGHT RESISTANT" 6. WHERE IS GAS BOND & PLEASE UNCOVER GROUND RODS 7. PLEASE ADD NEW CIRCUITS TO PLANS OR PULL A PERMIT FOR KITCHEN REMODEL. |