Permit: T07EL00027

Parcel: 133050210


Addresses:

8720 E LANCASTER RD

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/08/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. CHASE NIPPLE NOT ALLOWED FOR USE WITH L.L
2. BOND BUSHING NEEDED AT JUNCTION BOX
3. L.L & BOX TO BE CAPABLE OF BEING LOCKED ON SERVICE FEED SIDED
4. BRACING FOR RISER TO BE A RIGID SUPPORT KIT
5. CONDUCTOR TO BE MARKED "SUNLIGHT RESISTANT"
6. WHERE IS GAS BOND & PLEASE UNCOVER GROUND RODS
7. PLEASE ADD NEW CIRCUITS TO PLANS OR PULL A PERMIT FOR KITCHEN REMODEL.