Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07EL00018

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/08/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
02/08/2007 ELECTRIC - SERVICE UPGRADE Denied RISER MUST BE SCHEDULE 80 OR RIDGID
GROUND RODS MINIMUM 6' SEPERATION
SECURE RISER AT SUB PANEL
LABEL ALL CIRCUITS
01/05/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PLEASE UNCOVER CONDUIT RUN FOR INSPECTION
2. ABOVE GRADE TO BE SCHEDULE 80
3. PLEASE VERIFY GROUNDING ELECTRODE SYSTEM.
4. A PERMANENT METAL ADDRESS LABEL IS NEEDED.
5. OLD ALL-IN-ONE PANEL FOR SERVICE EQUIPMENT ONLY NOT ALLOWED AS A SUB-PANEL PER MANUFACTURES LISTING LABEL.