Permit: T07EL00008

Parcel: 131031490


Addresses:

5202 E 27TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/27/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/16/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
03/15/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) FINISH INSTALLING BOND TO GAS AND WATER PIPE
2) RECALL FOR FINAL AFTER TEP TIES INTO NEW SERVICE
03/13/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST SUPPORTS
2. INSTALL 2 GROUND RODS MIN. 6' APART
3. BLANK OPENINGS IN DEAD FRONT
4. BOND GAS & WATER PIPES
5. LABEL CIRCUITS IN PANEL