Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/16/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 04/25/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RISER BRACE MUST BE A LISTED ASSEMBLY, HOMEMADE OUT OF SMASHED ENDS OF EMT NOT APPROVED. 2. ALL CIRCUIT BREAKERS MUST BE OF SAME BRAND AS PANEL MANUF. 3. #2 FOOTER INSTALL 100 AMP BREAKER 4. OK GROUNDING 5. ALL CIRCUIT BREAKERS MUST BE OF SAME MANUF. AS SUB-PANELS. REMOVE CLOSET INSIDE STORAGE ROOM INSIDE HOUSE TO INSPECT SUB-PANEL. 6. RISER CONDUCTORS MUST BE SUNLIGHT RESISTANT MARKED ON INSULATION SER CABLE NOT APPROVED FOR RISER CONDUCTORS. |