Permit: T07EL00007

Parcel: 119041740


Addresses:

3502 S 9TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/21/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/16/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
04/25/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RISER BRACE MUST BE A LISTED ASSEMBLY, HOMEMADE OUT OF SMASHED ENDS OF EMT NOT APPROVED.
2. ALL CIRCUIT BREAKERS MUST BE OF SAME BRAND AS PANEL MANUF.
3. #2 FOOTER INSTALL 100 AMP BREAKER
4. OK GROUNDING
5. ALL CIRCUIT BREAKERS MUST BE OF SAME MANUF. AS SUB-PANELS. REMOVE CLOSET INSIDE STORAGE ROOM INSIDE HOUSE TO INSPECT SUB-PANEL.
6. RISER CONDUCTORS MUST BE SUNLIGHT RESISTANT MARKED ON INSULATION SER CABLE NOT APPROVED FOR RISER CONDUCTORS.