Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/05/2007 | ELECTRIC - FINAL | Approved | ||
| 01/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SECURE SERVICE TO STRUCTURE - PLASTIC DRYWALL ANCHORS NOT EFFECTIVE - SAME WITH GUTTER & STRUT ANCHORS. 2. GROUND METAL GUTTER 3. SERVICE MOUNTED TO HIGH 4. BOND WATER TO SERVICE 5. BURY GROUNDING ELECTRODE CONDUCTOR OR SECURE TO STRUCTURE. 6. IDENTIFY WHITE USED AS HOT 7. HOW WILL SPLICES BE MADE IN ATTIC - PROVIDE ACCESS |