Case: T07DV09812

Parcel: 12412293A


Addresses:

301 S PARK AV


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T07DV09812

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
08/18/2007 INSP - INITIAL CODE ENFORCMENT Approved MAIN FEEDER FOR WASTEWATER IS SHUT OFF DUE TO FIRE IN SERVICE PANEL 240
FIRE ISOLATED TO SERVICE PANEL
SERVICE PANEL FEEDING WASTERWATER HAS BURNED CONDUCTORS.
200 AMP/ VOLT 240/ MAX 60 3 PHAZE SYSTEM
125 AMP FUSES (3) FEEDING PANEL MARKED (2)
NEEDED FOR WASTE WATER
INSPECTOR HAS INFORMED CHIEF ENGINEER PERMITS WILL BE REQUIRED FOR THIS WORK
SOME ADDED CONDUIT PROTRUDING FROM PANEL (2)
APPEARS TO BE DONE IN A HAZARDOUS MANNER
PERMITS WILL BE REQUIRED TO ENSURE PROPERT WORK IS DONE PRIOR TO POWERING 1 2 3 PANELS

BURNED AND FRIED CONDUCTOR STEMING FROM RISER

NOV WRITTEN