Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07DV07899

Parcel: 12906147A


Addresses:

2202 E 20TH ST


Inspection Status: Correction Required

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T07DV07899

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Correction Required

Date Description Inspector Results Comments
08/17/2007 INSP - INITIAL CODE ENFORCMENT Correction Required TFD call-out. Resident/Tenant was experiencing problems with her electrical system. Upon inspection I found a 60 amp service which had been double-lugged to add additional circuit(s). In addition the all connections were loose, creating an overheating condition which burnt the wiring and internal components of the service panel. I turned the main service off and called the property owner, Wayne Hardy, whom dispatched an licensed electrical contractor. Bob Blizzard Electtrical responded and replaced the existing, burnt panel with a temporary panel so the tenant would have service for the weekend. I explained the issues to Mr. Hardy and told him he would need to obtain a permit ASAP and replace/upgrade the electrical service to the home. He acknowledged the he understood. Follow up 10 days. dc