Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2007 | INSP - FOLLOW UP CODE ENFORCE | Approved | RESEARCHED COT PERMITS PLUS PROGRAM FOR REQUIRED PERMIT. COMBO PERMIT # T07CM03842 HAS BEEN ISSUED ON 09/24/07. SEVERAL INSPECTIONS HAVE BEEN COMPLETED & ALL ITEMS ON NOV ISSUED ON 08/15/07 HAVE BEEN ADDRESSED. MARK CASE COMPLIANCE. [THESE NOTES ALSO AVAILABLE IN SIRE] | |
| 07/23/2007 | INSP - FOLLOW UP CODE ENFORCE | Approved | WHILE ON SITE, OCCUPANT OF STRUCTURE ARRIVED ON SITE. INFORMED TENANT DNR INSPECTOR WAS ON SITE FOR FOLLOW UP INSPECTION. TENANT ALLOWED ENTRY INTO STRUCTURE. INSPECTION FOUND THE FOLLOWING VIOLATIONS: INTERIOR FEATURES: 1) 6' X 4' SECTION OF DRYWALL HAS COLLAPSE AND HAS EXPOSED CEILING RAFTERS ELECTRICAL SYSTEMS 1) SEVERAL RECEPTACLES WERE FOUND LACKING COVER PLATES, SWITCH PLATES ALSO 2) HAZARDOUS ELECTRICAL - BROKEN RECEPTACLE BEHIND REFRIGERATOR 3) HAZARDOUS ELECTRICAL - CEILING LIGHT FIXTURE BANGING FROM CONDUCTORS WITH ILLEGAL SPLICE. 4) 60 AMP SERVICE HAS BEEN MODIFIED IN A HAZARDOUS MANNER. 60 AMP SERVICE HAS BEEN DOUBLE LUGGED. 5) W/O/P SUB PANEL AND RECEPTACLE HAVE BEEN ADDED, SUB PANEL HAS NO DIRECTORY & ELECTRICAL CONDUCTOR LACKS REQUIRED PROTECTION. 6) 220 OUTLET LACKING REQUIRED WEATHER PROTECTION FIRE SAFETY 1) STRUCTURE LACKS WORKING SMOKE DETECTOR MECH W/O/P 1) REPLACED WALL MOUNTED UPDUCT FURNACE. EXTERIOR FEATURES ROOFING ROOFING HAS BEEN DAMAGED BY WINDS. LARGE SECTION AL ROLL ROOFING W/COUTING HAS BEEN TORN AWAY MEAASURING APPROX 40 FT BY 10 FT. WOOD SURFACE HAS BEEN EXPOSED. REPAIR WILL REQUIRE INSPECTION UNDER PERMIT. PICTURES WERE TAKEN. -TEMP1 |