Case: T07DV05968

Parcel: 122132470


Addresses:

4141 E LEE ST #02


Inspection Status: Violation

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T07DV05968

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Violation

Date Description Inspector Results Comments
06/28/2007 INSP - INITIAL CODE ENFORCMENT Violation HEATING UNIT INSTALLED IN THE LIVING ROOM AREA WITHOUT PERMIT
SMOKE DETECTOR INOPERABLE
WINDOW IN THE BEDROOM WILL NOT OPEN TO ALLOW SAFE EGRESS IN CASE OF A FIRE
BATHROOM OUTLET HAS BEEN REPLACED WITH A 3 WIRE OUTLET AND SHOWS OPEN GROUND. LACKS GFCI PROTECTION. LIVING ROOM OUTLET ON SOUTH SIDE HAS CORD USED AS PERMANENT WIRING. MAIN ELECTRICAL PANEL LOCATED IN THE WASHROOM LACKS COVER AND PROPER LABELING. BREAKERS ARE VERY LOOSE. UNABLE TO DETERMINE TYPE AND CAPACITY OF BREAKERS.
COOLER IS LEAKING EXCESSIVE AMOUNTS OF WATER. COOLER IS SEVERLY DETERIORATED.
STOVE IS INOPERABLE
TOILET FLUSH HANDLE IS BROKEN. KITCHEN SINK IS NOT CONNECTED TO AN APPROVED DRAIN. DRAINS THROUGH WALL INTO A BASIN INSIDE THE WASHROOM. NO ACCESS TO WATER HEATER. DOOR IS NAILED SHUT.
WINDOWS ON THE EAST SIDE OF THE UNIT ARE BROKEN. PHOTOS TAKEN. RM