Inspection History: INSP - FOLLOW UP CODE ENFORCE
Case Number - T07DV02778
Inspection Description - INSP - FOLLOW UP CODE ENFORCE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2007 | INSP - FOLLOW UP CODE ENFORCE | Approved | ALL WORK COMPLETE. BACK TO ORIGINAL WIRING. - -TEMP1 | |
06/18/2007 | INSP - FOLLOW UP CODE ENFORCE | Approved | FOUND ALL ELECTRICAL PLUGS AND WIRING APPROVED IN 0987. J-BOX ONLY TO BE REMOVED - -TEMP1 | |
05/15/2007 | INSP - FOLLOW UP CODE ENFORCE | Approved | ILLEGAL WIRING REMOVED. ALL WOOD FLOORING REMOVED. - -TEMP1 | |
03/30/2007 | INSP - FOLLOW UP CODE ENFORCE | Violation | LIGHT FIXTURES INSTALLED IN STORAGE AND MANUFACTURING AREA WITHOUT PERMITS. EXPOSED ROMEX WRAPPED AROUND METAL BEAMS. PLATFORMS INSTALLED ON SHELVING BEAMS USING 2X6 AND PLYWOOD WITHOUT PERMITS. EXTENSION CORDS HANGING FROM THE CEILING, CONNECTED TO IMPROPERLY MOUNTED JUNCTION BOXES THEN POWERING EQUIPMENT. ELECTRICAL PANEL LOCATED ON THE NORTH WALL IN STORAGE AREA IS OBSTRUCTED. GAS SUPPLY SYSTEM HAS BEEN MODIFIED WITHOUT PERMITS AND IS UNSAFELY SECURED BY A 2X4. PHOTOS TAKEN. RM |