Case: T07DV00985

Parcel: 11008065A


Addresses:

2626 N COLUMBUS BL

Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Date Description Inspector Results Comments
02/07/2007 INSP - FOLLOW UP CODE ENFORCE Approved WATERLINE FIXED. LIGHT REMOVED FROM ABOVE SINK. - Mel
12/28/2006 INSP - FOLLOW UP CODE ENFORCE Violation BROKEN WATER LINE IN THE KITCHEN FLOODED UNIT. WATER SHUT OFF BY TFD. CONTACTED TEP TO CAP ELECTRICAL SERVICE. WALLS WET NEAR ELECTRICAL CIRCUITS AND STANDING WATER APPROX 3 INCHES IN THE LIVING ROOM AREA. ELECTRICAL OUTLET NEAR SINK IS NON GFCI PROTECTED. LIGHT FIXTURE INSTALLED NEXT TO SINK. GROUND WIRE ON REFRIGERATOR HAS BEEN CUT TO FIT TWO PRONG OUTLET. UNIT LACKS SMOKE DETECTORS. LIVING ROOM ROOF LEAKING. BEDROOM ILLEGAL CONNECTION OF LIGHT FIXTURE TO J-BOX IN THE CEILING. ADDED ELECTRICAL OUTLET ON THE WEST WALL. ROOF LEAKING. BATHROOM ELECTRICAL OUTLET INSTALLED NEXT TO WATER LINE AND LACK GFCI PROTECTION. UNIT VACATED AND POSTED DO NOT ENTER. TENANT HAD BEEN EVICTED AND STATED DID NOT NEED PLACEMENT ASSISTANCE. PHOTOS TAKEN. RM