Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL 1. FILL AROUND BOXES WITH DRYWALL MUD - 314.21 2. FILL UNUSED OPENINGS IN FIXTURES |
|
| 07/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* EVIDENCE TO WORK NOT MEETING CODES NO PAPERWORK TO ALLOWING COVERING OF DRYWALL PLEASE CALL 791-5550 ASK FOR PERMIT COUNTER AND ADD 02035 PERMIT HAVE ELECTRICIAN ON SITE |
|
| 06/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DRYWALL INSTALLED BEFORE APPROVAL TO BE REMOVED 2. ELECTRICAL CONTRACTOR TO BE ON SITE FOR INSPECTION REFEE TO BE PAID |
|
| 05/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. CLOSE UNUSED OPENINGS IN BOXES - 110.12A 2. PROVIDE NAIL PLATES FOR MC WHERE HOLE IS LESS THAN 1 1/4" FROM STUD FACE -- 300.4 3. EMT TO BE SECURED WITHIN 12" OF ENCLOSURES - 358.30 4. WIRING NOT PER PLAN, NOT COMPLETE, HAVE OPEN WIRING 5. PROVIDE ACCESS TO ATTIC WIRING 6. CHECK J-BOX FILL -- 314.16 |
|
| 04/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RON @ 954-2095 SPUD @ 248-9700 JOB IS NOT READY FOR ELECTRICAL FINAL NEED A LICENSED ELECTRICAL CONTRACTOR TO GO THROUGH AND MAKE SURE INSTALLATION IS PER APPROVED PLAN AND PER NATIONAL ELECTRIC CODE. |