Permit: T07CM04843

Parcel: 14002010A


Addresses:

3950 E IRVINGTON RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/15/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/14/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
FIRE DAMPERS NOT SHUTTING WITH SMOKE TEST
EVERYTHING ELSE IS OK
05/01/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- REMOVE ANGLE IRON FROM FIRE DAMPERS.
- NEED TO SEE MIN. CLEARANCES
- PROVIDE ANGLE IRON FOR FIRE DAMPERS WITH GRILLE
- PROVIDE A TRAP ON CONDENSATE DRAIN LINES AC 3 & 4
- PROVIDE A MIN. 100 PSI HYDROSTATIC TEST ON ALL CHILLER PIPING
- NEED TO TEST FIRE SMOKE DAMPERS
- PROVIDE INSTALL INSTRUCTIONS FOR DAMPERS
- WHERE IS ACCESS TO BLOWER MOTOR FOR ABOVE CEILING FAN COILS?
- REMOVE SECONDARY DRAIN PANS IF NECESSARY & PROVIDE OVERFLOW SENSOR IN PRIMARY DRAIN PAN.

AC 1,2,3,4 NOT CARRIER AS PER PLANS