Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04843
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EM LIGHTING NOT WORKING 2. BONDING JUMPERS TO BE SIZED PER NEC 250.122 3. GROUNDING COMPUTER ROOM NOT PER PLAN 4. NEED DISCONNECTS FOR AC UNITS 5. NEED SYSTEM BONDING JUMPER FOR GENERATOR 6. NEED REVISED SET OF PLANS |
|
05/15/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED TO HAVE FIELD EVALUATION BY NRTL ON 2 SWITCHBOARDS WITH 3 SETTINGS EACH. RECALL FOR FINAL ON SAME DAY AS FIELD EVALUATION. 2. HAVE EQUIPMENT OPEN FOR FINAL |