Permit: T07CM04843

Parcel: 14002010A


Addresses:

3950 E IRVINGTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04843

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/30/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EM LIGHTING NOT WORKING
2. BONDING JUMPERS TO BE SIZED PER NEC 250.122
3. GROUNDING COMPUTER ROOM NOT PER PLAN
4. NEED DISCONNECTS FOR AC UNITS
5. NEED SYSTEM BONDING JUMPER FOR GENERATOR
6. NEED REVISED SET OF PLANS
05/15/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEED TO HAVE FIELD EVALUATION BY NRTL ON 2 SWITCHBOARDS WITH 3 SETTINGS EACH. RECALL FOR FINAL ON SAME DAY AS FIELD EVALUATION.
2. HAVE EQUIPMENT OPEN FOR FINAL