Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM04843
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/30/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/25/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. LB'S ABOVE RPMB NOT SIZED PROPERLY LB'S STAMPED WITH MAX # OF CONDUCTORS ALLOWED 2. LISTING OF SWITCHBOARDS SHOWS EACH SECTION TO BE 1 OF 1 WHEN EACH SWITCHBOARD IS A 3 SECTION SWITCHBOARD. SHOULD BE MARKED 1 OF 3, 2 OF 3, 3 OF 3 MAY NEED TO HAVE FIELD EVALUATION DONE BY NRTL 3. FEEDERS BY OTHERS NOT COVERED UNDER THIS ACTIVITY DOES NOT SHOW SIZING OR LOCATION OF SOURCE 4. OK CEILING IN COMMAND CENTER |
|
04/01/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILINGS RMS 101, 103 |