Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2008 | ELECTRIC - FINAL | Approved | INSTALLATION UP TO EQUIPMENT DISCONNECTS COMPLETE PER R. HOLLANDER. EQUIPMENT ACCEPTED PER NEC ARTICLE 670 AND FIELD OBSERVATION BY PROFESSIONAL ENGINEER. ENGINEER REPORT COPIED AND FILED WITH RECORDS. | |
| 07/30/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* MODIFY LETTER |
|
| 07/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #1 |
|
| 07/16/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #1 & #3 |
|
| 07/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT TO BE LISTED & LABELED 110.3 2. PANEL DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATIONS 3. BOXES MORE THAN 1/4" FROM BOXES TO SURFACE - 314.20 4. EM LIGHTS & EXITS TO BE AS PER 700.12 5. LETTER FROM ENGINEER TO MEET ACIL STANDARDS FOR TESTING OF EQUIPMENT - NOT ACCEPTED AS WRITTEN. |
|
| 03/19/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* DO NOT CALL BEFORE APPROVED OR A FEE WILL BE CHARGED |
|
| 03/14/2008 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |