Permit: T07CM04827

Parcel: 133380630

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/29/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEED MEYERS HUB OR INSULATING, LOCK NUT AT CONDUIT CONNECTION MAIN PANEL
2) VACUUM BREAKER ON HOSE BIB
3) OK TO INSULATE AND SHEETROCK
06/04/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ADD RECEPTACLE WEST WALL FAMILY NEAR SHOWER
2) USE NO LOX ON ALUMINUMN WIRE CONNECTIONS
3) #2 ALUMINIUM IS GOOD FOR 90 AMPS
4) INSTALL VACUUM BREAKER ON HOSE BIB
5) GAS BOND MUST BE ACCESSIBLE
05/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CONDUIT AND BOXES FOR GARAGE ELECTRIC OK