Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING ELECTRODES & GROUNDING ELECTRODE CONDUCTOR TO BE INSTALLED FOR XFMRS 2. CONNECTIONS TO BE ELEVATED 12" OFF OF GROUND OUTDOORS 3. INSTALL STRAIN RELIEF ON CABLE COMING OUT OF SERVICE DISCONNECTS 4. NEXT YEARS SHOW WILL REQUIRE LISTING OF PANELS, XFMRS AND POWER DISTRIBUTION EQUIPMENT 5. CHECK RECEPTACLES HAVE REVERSE POLARITY AND ALL LIGHTS ARE LIT ON PLUG TESTER 6. CHECK EM. LIGHTING & MARK LIGHTING CIRCUITS @ PANELS 7. RECALL WHEN READY |