Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 03/28/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT VDV CABLING 725.25, 800.25, 300.11 CANNOT SUPPORT OFF OF M/C CABLES 2. BOX OVERFILLED 3. SUPPORT M/C CABLES PER 330.30 4. SECURELY ATTACH FIXTURES TO GRID 410.16 5. SUPPORT CONDUITS AS PER CODE - WITHIN 3' OF BOXES 6. FILL UNUSED OPENING - CONDUIT ABOVE PANEL 7. PLEASE ADD SUITE # TO PERMIT |