Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
04/01/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/28/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT VDV CABLING 725.25, 800.25, 300.11
CANNOT SUPPORT OFF OF M/C CABLES
2. BOX OVERFILLED
3. SUPPORT M/C CABLES PER 330.30
4. SECURELY ATTACH FIXTURES TO GRID 410.16
5. SUPPORT CONDUITS AS PER CODE - WITHIN 3' OF BOXES
6. FILL UNUSED OPENING - CONDUIT ABOVE PANEL
7. PLEASE ADD SUITE # TO PERMIT