Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM04797

Parcel: 141220290


Addresses:

8940 E RITA PARK DR


Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T07CM04797

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
12/04/2008 FIRE SPKLR - UG, PIPING, HYDRO Approved UNDER PERMIT T08BU00867
06/05/2008 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Riser #4 stub - APPROVED
UG #7 to Riser #14 - both ends to be uncovered to stub out and tee's on main line - APPROVED
UG #5 to Riser #12 - both ends to be uncovered to stub out and tee's on main line - APPROVED
TEE'S Ok, but unable to see 90 deg elbows to stubs because of concrete poured all around. All ductile iron pipe that was uncovered was wraped with black plastic. STILL NEED TO PRESSURE TEST PIPE AT 200psi FOR 2 HOURS.
Also posted on permits T07CM04797 & T07CM04127 & T08BU00867
06/04/2008 FIRE SPKLR - UG, PIPING, HYDRO Denied UG 10 TO RISER #6
06/03/2008 FIRE SPKLR - UG, PIPING, HYDRO Denied UG 14 to riser #1 - APPROVED
D1 6" line - APPROVED
B #5 10" line - APPROVED
06/02/2008 FIRE SPKLR - UG, PIPING, HYDRO Denied All of the underground was buried expect approximately 100' on the west end was left open to inspect. Order was given to uncover 10 spots for visual inspection, the following areas are:
UG 14 to riser #1
Riser #4 stub
UG 11 to Riser #5
UG 10 to Riser #6
D1 6" line
B #5 10" line
UG #7 to Riser #14 - both ends to be uncovered to stub out and tee's on main line
UG #5 to Riser #12 - both ends to be uncovered to stub out and tee's on main line