Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04797
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/16/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. STILL NEED TO RELOCATE 6" WATER LINE 2. STILL NEED BALLARDS FOR PROTECTION 3. STILL NEED GENERATOR LETTER |
|
12/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK EM LIGHTING THROUGHOUT WAREHOUSE |
|
11/25/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK FINAL ADMIN. AREA 2. NEED PLAQUES @ SERVICES FOR MULTI-SERVICES AND GENERATOR 3. NEED PHYSICAL PROTECTION FOR ELECTRICAL EQUIPMENT 4. PROVIDE LETTER FOR TEST OF GENERATOR SYSTEM 5. NEED PANEL SCHEDULES 6. NEED TO TEST EM LIGHTING |
|
11/24/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED DISCONNECTING MEANS FOR FAN COIL UNITS @ REMOTE BATHROOMS 2. NEED DISCONNECTING MEANS FOR ICE MAKER @ REMOTE BATHROOMS. ALL ICE MAKERS. 3. INSTALL PLATE GARBAGE DISPOSAL RECEPT. TRACKERS BREAKROOM 4. MULTI-WIRE BRANCH CIRCUITS TO OFFICE FURNITURE TO HAVE HANDLE TIES 5. OFFICE FURNITURE SHOWING OPEN NEUTRAL 6. NEED DISCONNECTING MEANS FOR INSTANT HOT 7. OK CMMS OFFICE 8. WALK THRU OF GUARD HOUSE, CMMS, REMOTE RESTROOMS, PUMP HOUSE, INBOUND & TRUCKERS BREAK AREA |
|
08/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ADMIN. & PERSONNEL 1. SOME RECEPTACLES HAVE NO POWER 2. FINISH POWER POLES/WIRING OF FURNITURE 3. MULTI-WIRE CIRCUITS TO OFFICE FURNITURE NEED APPROVED HANDLE TIES 4. RECEPTACLE FOR TV TO BE BELOW DROP CEILING NO LOADS ABOVE CEILING 5. ENSURE RECEPTACLES EXTEND PAST METAL FACE PLATES 6. OK HARD LID EQUIPMENT ROOM 203 |
|
08/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK NORMAL & EMERGENCY LIGHTING 1ST & 2ND FLOOR PERSONNEL AND ADMIN. |