Permit: T07CM04797

Parcel: 141220290


Addresses:

8940 E RITA PARK DR


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM04797

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/16/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/24/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. HAVE SPRINKLER PIPING ABOVE ELECTRICAL EQUIPMENT IN PUMP HOUSE THIS IS DEDICATED SPACE ABOVE EQUIPMENT AND PIPING NEEDS TO BE MOVED NEC 110.26
2. OK MAKE UP XFMR TNL5, TNL8, TNL13
10/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK 45KVA TRANSFORMER AT GUARD HOUSE
2. RECEIVED LETTER OF TORQUE FOR MSB-1
10/24/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO CLEAR TEC COMMERCIAL METER #1 & #2

CALLED TEP MAP ROOM WITH CLEARANCE

1. SERVICE INSPECTION FOR NEW SECTION ADDED
TO 13.8 SWITCH
2. RECEIVED CHECK #209883 FOR $150.00 FOR SATURDAY INSPECTION.
10/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK CEILINGS GUARD HOUSE
2. OK PUMP HOUSE PRIMARY XFMR #4
3. OK PRIMARY #1 XFMR
4. OK FIRE PUMP CONTROLLER AND SERVICE DISCONNECT @ PUMP HOUSE
10/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANEL NH9, NH9A, NL9C, NL9A, NL9B @ B13
2. OK TRANSFORMERS, TNL9, TNL9C @ B13
3. HAVE DUCT WORK IN EQUIPMENT DEDICATED SPACE NEEDS TO BE MOVED
10/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO ENERGIZE MSB-1
2. OK PANEL NH1-B, NH7, PH
10/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WIRING TO ROOFTOP UNITS EAST OF MFL WALL EXCEPT RTU-19 AND RTU-15
10/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FEEDER MAKE UP TO CP-4, CP-6, CP-7, CP-8, CP-9
10/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK RELOCATED POLE BASE
2. OK WIRING TO BOILER
3. OK FEEDER TERMINATION CP-1, CP-2, CP-3
09/30/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
ELECTRICAL CONTRACTOR NOT ON SITE 4:25 P.M.
09/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. MEETING TO DISCUSS PROJECT
2. 3RD FLOOR PICK MOD LIGHTING OK
09/16/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANELS NH21A & B, NH31A & B, NH11A & B
2. OK PANELS CP-4, CP-5, CP-6
3. OK MAKE UP TO EH-4
4. OK WALLS EAST REMOTE BATHROOM. CMMS OFFICE.
5. OK ROOFTOP UNITS WEST OF MFL WALL
08/29/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
08/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK MAKEUP XFMR T-UPSL2
2. OK WALLS TRUCKER BREAK AREA
3. OK MAKEUP XFMR T-RT15
08/27/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
ELECTRICAL CONTRACTOR NOT ON SITE 3:25 PM
08/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/16/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/14/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK LIGHTING, BOXES AND RACEWAYS
3RD LEVEL MEZZ. ROWS 104
FAST PICK
2. OK LIGHTING, BOXES AND RACEWAY
3RD LEVEL MEZZ CENTER SECTION
08/12/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
ELECTRICAL CONTRACTOR NOT ON SITE - 3:25 PM
08/11/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK DROP CEILINGS FIRST FLOOR EXCEPT ENTRY AREA
2. OK HARD LIDS 2ND FLOOR
3. OK PANELS, XFMRS AND FEEDERS AS INDICATED ON
PLANS E-603
NH12 GROUP AND NH3
08/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WIRING TO RTU 39, 40, 41, 42, 43 & 44
2) RACEWAYS TO BE CONTINOUS TO RTU'S SEE NEC 300.10 AND 300.12
3) SEAL RACEWAYS INTO UNITS PER INSTRUCTIONS AND NEC 300.7
08/05/2008 ELECTRIC - INTERMEDIATE Partial Approval INSPECTION OF MSB-3
08/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ENERGIZE MSB-3 ELECTRICAL CONTRACTOR TO ENSURE ONLY QUALIFIED PERSONS ENERGIZE EQUIPMENT WHEN READY TO USE LOCK OUT PROCEDURES
08/01/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO ENERGIZE MSB2 ELECTRICAL CONTRACTOR TO ENSURE ONLY QUALIFIED PERSONS TO TURN ON ANY PANEL OR BRANCH CIRCUITS. USE LOCK OUT PROCEDURES
2. OK FEEDERS TO TNL-16, TNL-15, NH6, NL2, MCC2 (C4)
07/31/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANELS, FEEDERS AND XFMRS AS INDICATED ON E602
2. OK 13.8 TRANSFORMERS #2 & #3
07/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK FEEDERS & PANELS AS INDICATED ON PLAN E604 & E603
2. OK WALLS GUARD HOUSE INSTALL NAIL PLATES AS DISCUSSED
3. CHECK ON BREAKER SIZES @ GEN. FEEDS TO ATS
07/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FEEDERS TO NH4-A1, NH11A, NH11B, NL11A, NL11B, NL11C
NH2B, NH2A
07/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
START OF INSPECTIONS ON SERVICES
- NEED TO HAVE GFI PERFORMANCE TEST ON SERVICES
- NEED LETTER OF TORQUE
- HAVE REDUCED SET OF PLANS FOR INSPECTIONS
07/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ENERGIZE LEIBERT AC UNITS IN UPS ROOM AND COMPUTER ROOM WITH TEMP GENERATOR.
NEED 15 AMP OVERCURRENT PROTECTION FOR FAN COIL UNITS ON ROOF
07/23/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & HARD LIDS WEST REMOTE BATHROOM
07/14/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
07/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSPECTION OF MEDIUM VOLTAGE SWITCHGEAR
A. PARSONS TO LOCK OUT BREAKERS TO XFMRS
B. CANNOT ENERGIZE ANY EQUIPMENT BEYOND MEDIUM VOLTAGE SWITCH
C. BOND REQUIREMENT WAIVED PER
DIRECTOR ERNIE DUARTE
07/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ADMIN. MEZZANINE
07/01/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
06/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK HARD LIDS RMS. 113, 114A, 114, 115, 117, 118, 139, 140
2. OK WALLS 2ND FLOOR RMS. 216-222, 224-230, RM. 205
3. OK POLE BASE (5) AS INDICATED ON E101
06/27/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
06/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANEL WALL RM 113
2. OK WALLS 1ST FLOOR PERSONNEL AREA
06/09/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RMS 117, 118, 129, 129A, 131, 140, 139, 134, 132, 124, 121, 122, 106, 107
06/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RMS. 114A, 114, 115, 113, 132, 134
06/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RMS. 104, 105, 103 AND CAFE AS INDICATED ON PLAN E403
06/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RMS 125-128
05/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RMS. 137 & 138
05/14/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK HOME RUNS MC CABLE 2ND FLOOR SLAB PERSONNEL OFFICE