Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM04797
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/24/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. HAVE SPRINKLER PIPING ABOVE ELECTRICAL EQUIPMENT IN PUMP HOUSE THIS IS DEDICATED SPACE ABOVE EQUIPMENT AND PIPING NEEDS TO BE MOVED NEC 110.26 2. OK MAKE UP XFMR TNL5, TNL8, TNL13 |
|
10/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK 45KVA TRANSFORMER AT GUARD HOUSE 2. RECEIVED LETTER OF TORQUE FOR MSB-1 |
|
10/24/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO CLEAR TEC COMMERCIAL METER #1 & #2 CALLED TEP MAP ROOM WITH CLEARANCE 1. SERVICE INSPECTION FOR NEW SECTION ADDED TO 13.8 SWITCH 2. RECEIVED CHECK #209883 FOR $150.00 FOR SATURDAY INSPECTION. |
|
10/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK CEILINGS GUARD HOUSE 2. OK PUMP HOUSE PRIMARY XFMR #4 3. OK PRIMARY #1 XFMR 4. OK FIRE PUMP CONTROLLER AND SERVICE DISCONNECT @ PUMP HOUSE |
|
10/20/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANEL NH9, NH9A, NL9C, NL9A, NL9B @ B13 2. OK TRANSFORMERS, TNL9, TNL9C @ B13 3. HAVE DUCT WORK IN EQUIPMENT DEDICATED SPACE NEEDS TO BE MOVED |
|
10/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK TO ENERGIZE MSB-1 2. OK PANEL NH1-B, NH7, PH |
|
10/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WIRING TO ROOFTOP UNITS EAST OF MFL WALL EXCEPT RTU-19 AND RTU-15 |
|
10/06/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FEEDER MAKE UP TO CP-4, CP-6, CP-7, CP-8, CP-9 |
|
10/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK RELOCATED POLE BASE 2. OK WIRING TO BOILER 3. OK FEEDER TERMINATION CP-1, CP-2, CP-3 |
|
09/30/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* ELECTRICAL CONTRACTOR NOT ON SITE 4:25 P.M. |
|
09/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. MEETING TO DISCUSS PROJECT 2. 3RD FLOOR PICK MOD LIGHTING OK |
|
09/16/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
09/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANELS NH21A & B, NH31A & B, NH11A & B 2. OK PANELS CP-4, CP-5, CP-6 3. OK MAKE UP TO EH-4 4. OK WALLS EAST REMOTE BATHROOM. CMMS OFFICE. 5. OK ROOFTOP UNITS WEST OF MFL WALL |
|
08/29/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |
|
08/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK MAKEUP XFMR T-UPSL2 2. OK WALLS TRUCKER BREAK AREA 3. OK MAKEUP XFMR T-RT15 |
|
08/27/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* ELECTRICAL CONTRACTOR NOT ON SITE 3:25 PM |
|
08/21/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/16/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/14/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK LIGHTING, BOXES AND RACEWAYS 3RD LEVEL MEZZ. ROWS 104 FAST PICK 2. OK LIGHTING, BOXES AND RACEWAY 3RD LEVEL MEZZ CENTER SECTION |
|
08/12/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* ELECTRICAL CONTRACTOR NOT ON SITE - 3:25 PM |
|
08/11/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK DROP CEILINGS FIRST FLOOR EXCEPT ENTRY AREA 2. OK HARD LIDS 2ND FLOOR 3. OK PANELS, XFMRS AND FEEDERS AS INDICATED ON PLANS E-603 NH12 GROUP AND NH3 |
|
08/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WIRING TO RTU 39, 40, 41, 42, 43 & 44 2) RACEWAYS TO BE CONTINOUS TO RTU'S SEE NEC 300.10 AND 300.12 3) SEAL RACEWAYS INTO UNITS PER INSTRUCTIONS AND NEC 300.7 |
|
08/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | INSPECTION OF MSB-3 | |
08/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO ENERGIZE MSB-3 ELECTRICAL CONTRACTOR TO ENSURE ONLY QUALIFIED PERSONS ENERGIZE EQUIPMENT WHEN READY TO USE LOCK OUT PROCEDURES |
|
08/01/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK TO ENERGIZE MSB2 ELECTRICAL CONTRACTOR TO ENSURE ONLY QUALIFIED PERSONS TO TURN ON ANY PANEL OR BRANCH CIRCUITS. USE LOCK OUT PROCEDURES 2. OK FEEDERS TO TNL-16, TNL-15, NH6, NL2, MCC2 (C4) |
|
07/31/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANELS, FEEDERS AND XFMRS AS INDICATED ON E602 2. OK 13.8 TRANSFORMERS #2 & #3 |
|
07/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK FEEDERS & PANELS AS INDICATED ON PLAN E604 & E603 2. OK WALLS GUARD HOUSE INSTALL NAIL PLATES AS DISCUSSED 3. CHECK ON BREAKER SIZES @ GEN. FEEDS TO ATS |
|
07/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FEEDERS TO NH4-A1, NH11A, NH11B, NL11A, NL11B, NL11C NH2B, NH2A |
|
07/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* START OF INSPECTIONS ON SERVICES - NEED TO HAVE GFI PERFORMANCE TEST ON SERVICES - NEED LETTER OF TORQUE - HAVE REDUCED SET OF PLANS FOR INSPECTIONS |
|
07/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO ENERGIZE LEIBERT AC UNITS IN UPS ROOM AND COMPUTER ROOM WITH TEMP GENERATOR. NEED 15 AMP OVERCURRENT PROTECTION FOR FAN COIL UNITS ON ROOF |
|
07/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & HARD LIDS WEST REMOTE BATHROOM |
|
07/14/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |
|
07/11/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSPECTION OF MEDIUM VOLTAGE SWITCHGEAR A. PARSONS TO LOCK OUT BREAKERS TO XFMRS B. CANNOT ENERGIZE ANY EQUIPMENT BEYOND MEDIUM VOLTAGE SWITCH C. BOND REQUIREMENT WAIVED PER DIRECTOR ERNIE DUARTE |
|
07/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ADMIN. MEZZANINE |
|
07/01/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |
|
06/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK HARD LIDS RMS. 113, 114A, 114, 115, 117, 118, 139, 140 2. OK WALLS 2ND FLOOR RMS. 216-222, 224-230, RM. 205 3. OK POLE BASE (5) AS INDICATED ON E101 |
|
06/27/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |
|
06/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANEL WALL RM 113 2. OK WALLS 1ST FLOOR PERSONNEL AREA |
|
06/09/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS RMS 117, 118, 129, 129A, 131, 140, 139, 134, 132, 124, 121, 122, 106, 107 |
|
06/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS RMS. 114A, 114, 115, 113, 132, 134 |
|
06/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS RMS. 104, 105, 103 AND CAFE AS INDICATED ON PLAN E403 |
|
06/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS RMS 125-128 |
|
05/21/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS RMS. 137 & 138 |
|
05/14/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HOME RUNS MC CABLE 2ND FLOOR SLAB PERSONNEL OFFICE |