Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM04788
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/27/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/25/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE DUCT SMOKE DETECTOR REPORT 2. PROVIDE PROPER CONDENSATE DRAIN FALL |
|
| 08/11/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE HAIL GUARDS ON AC UNITS AS PER PLANS 2. PROVIDE AIR BALANCE REPORT 3. MARK UNIT DATA PLATES W/PROPER HEAT STRIPS AND FUSE ACCORDINGLY 4. PERMANENTLY I.D EQUIPMENT 5. AUDIBLE & VISIBLE ALARMS ON DUCT SMOKE DETECTORS IS NOT AN OPTION. SEE SECTION 606.4.1 IMC |